To Understand CPO in Volume Production, First Understand Two Things: Electrical Reach and What Happens When the Laser Fails
1. Why every CPO conversation ends up at "what happens when the laser fails?"
On NVIDIA's November 17 earnings call, interim CEO Colette Kress said CPO (co-packaged optics) scale-out switches are "in volume production" and that NVIDIA will scale optics manufacturing capacity 15x in 2027. She gave three numbers: compared with pluggable optics, NVIDIA Photonics switches deliver 5x better power efficiency, 15x higher reliability and 10% lower latency. A day earlier, cloud provider Lambda said it had connected more than 10,000 Blackwell Ultra GPUs with CPO switches in Quebec, Canada.
It sounds like CPO has won. Yet the same NVIDIA release also listed USFP, a new pluggable form factor co-developed with Cisco. If CPO is already in production, why build a new pluggable? Readers tend to ask three questions:
Now that CPO is shipping, are pluggable optical modules on their way out?
CPO saves power, but where exactly does the saving come from?
CPO is supposed to be less reliable, so how can NVIDIA claim 15x higher reliability?
These questions usually start from the wrong place. People compare CPO and pluggables as two "products," but the real difference is two engineering choices. CPO saves power by making the electrical signal travel a shorter distance; the price is that the optics are sealed next to the switch chip and can no longer be pulled out and swapped like a module.
So this piece does not start with CPO products. It first explains two things: how far the electrical signal travels, and what happens when the laser fails. By the end, you will know the three questions to ask about any CPO, NPO or new pluggable headline.
2. A different yardstick: it is not about bandwidth, it is about "how far the signal travels and what you replace"
Many people think of CPO as "a faster optical module." On bandwidth alone, CPO and pluggable switches do the same job: NVIDIA's Quantum-X Photonics has 144 ports of 800G, and a Broadcom Tomahawk 6 switch delivers 102.4T whether it uses CPO or pluggables. The speed is the same. What differs is how far the electrical signal travels before it becomes light, and how big a piece you must replace when the optics fail.
The power of an optical link can be split roughly into two parts:
Power per port ≈ cost of getting the electrical signal to the optics (SerDes, retimer, DSP) + cost of turning electricity into light (laser, modulator, driver)
The second half is similar in both designs; nearly all the difference sits in the first half. That gives two ways to pay:
Pluggable: the electrical signal runs a long PCB trace from the switch chip to a module on the front panel, where a DSP repairs the distorted signal. You pay in power, and you get "pull it out and swap it" in return.
CPO: the optical engine sits right next to the switch chip on the package, the signal travels only millimeters before becoming light, and no DSP is needed. You save power, but the optical engine can no longer be removed on its own.
Remember this: the CPO-versus-pluggable debate is a trade between "saving power" and "easy to fix."
3. Thing one: how far the electrical signal travels (like pushing a cart on a muddy road: the longer the road, the harder the push)
3.1 Why a longer electrical path needs a DSP
A switch chip sends out electrical signals at 200G per lane. At that frequency, signals on copper fade fast: the longer the path, the flatter and blurrier the signal, so by the time it reaches the optical module a DSP (digital signal processor) or retimer has to restore it.
NVIDIA's March 2025 technical blog gave concrete numbers: in a traditional switch, the PCB trace from chip to front-panel module is about 14 to 16 inches (roughly 35 to 40 cm), while silicon-photonics CPO cuts it to less than 0.5 inch. Its August blog added the loss: the pluggable path loses up to about 22 dB on a 200G channel, versus about 4 dB for CPO.
This figure shows how far the electrical signal travels from the same switch chip before it becomes light: a pluggable crosses the whole board to the front panel; NPO pulls the optical engine to a few centimeters from the chip; CPO puts it right on the package. Each segment is labeled with its loss, and the higher the loss, the more a DSP is needed downstream.

▲ Electrical channel length and loss: pluggable, NPO and CPO (Image source: Simple Tech Trend original; data from NVIDIA, Samtec, Broadcom)
The gap between 22 dB and 4 dB is 18 dB. Decibels are logarithmic, so 18 dB is roughly a 63x power ratio. When NVIDIA's caption says "64x better signal integrity," this 18 dB is what it means (STT calculation).
This figure shows how NVIDIA explains CPO's electrical advantage: in the pluggable switch on top, the signal passes through the substrate, PCB, port cage and module, and each red dot is a loss point, adding up to 22 dB; in the CPO design below, only one stretch on the substrate remains, about 4 dB. The figure also notes another detail: a pluggable uses 8 lasers per 1.6T, while CPO uses only 2 continuous-wave lasers per 1.6T.

▲ Electrical loss, pluggable vs NVIDIA co-packaged silicon photonics (22 dB vs 4 dB) (Image source: NVIDIA Technical Blog, 2025-08-18)
3.2 Examples: how much power is saved
The DSP is the most power-hungry part of a pluggable module. NVIDIA estimates a 1.6T pluggable at about 30 W, with the DSP taking more than half. Broadcom's three generations of CPO switches give the most complete comparison:
Generation | Switch chip | Power per 800G port | pJ/bit (STT calculation) |
Pluggable (with DSP) | — | ~14–18 W | ~18–23 |
Humboldt (CPO gen 1) | Tomahawk 4 | ~6.4 W | ~8 |
Bailly (CPO gen 2) | Tomahawk 5 | 5.5 W | ~6.9 |
Davisson (CPO gen 3) | Tomahawk 6 | ~3.5 W | ~4.4 |
Davisson uses more than 70% less power per port than a pluggable. Meta's tests of Bailly point the same way: per 100G lane, CPO uses 65% less power than retimed pluggables and 35% less than linear pluggable optics (LPO), which already drop the DSP.
This figure shows Meta's measured power per 800G: the test used 120 optical engines and 240 laser source modules, against 48 pluggable modules from 4 vendors. Retimed pluggables drew about 15 W and Bailly CPO about 5.4 W, a 65% saving; per 100G lane, CPO was also 35% below LPO.

▲ Measured power per 800G, Broadcom Bailly CPO vs pluggables (Image source: Meta/Broadcom, "CPO Technology Evaluation for Hyperscale Data Center Fabric Switches," via The Next Platform, 2025-10-17)
Scale a single port up to a full cluster and the gap is obvious. The Next Platform estimates that for a 100,000-accelerator cluster, all-pluggable optics would draw about 192 MW, LPO about 64 MW and CPO about 42 MW, against roughly 400 MW for the GPUs themselves.
3.3 The price: the closer you push, the harder it is to take apart
A shorter electrical path saves power, but "short" has a cost. To keep the signal to a few millimeters, the optical engine must sit on the same package substrate as the switch chip, built with advanced packaging such as TSMC COUPE. NTT's PEC-2 photonics-electronics convergence device, shown at its R&D Forum in November, cut the electrical distance from about 30 cm to 3 cm the same way: by mounting the processor and optical engine on one base.
The Register spells out the cost: if one optical chiplet in a CPO switch fails, you might lose 8, 16, 32 or more ports at once. A failed pluggable takes out just 1 port. The shorter the electrical path, the more tightly the optics are bound to the chip; every watt saved is paid for with "can't take it apart."
That leads to thing two: if you can't take it apart, where do you put the part most likely to fail?
4. Thing two: what happens when the laser fails (like a light bulb: put the socket where you can reach it)
4.1 Why the laser is the part CPO most needs to be replaceable
Silicon does not emit light, so a silicon-photonics optical engine needs a separate InP (indium phosphide) laser to supply continuous light. The laser is the hottest component in the optical link and the one most prone to aging.
The Advanced Photonics Coalition (APC) CPO document caps the failure rate of a single laser source at 100 FIT (100 failures per billion hours), with a 10-million-hour median life. But FIT adds up: run 1,024 laser sources together and the system averages one failure about every 13 months. We worked through this math in "CPO laser specs are really about reliability."
So the CPO camp agrees: the optical engine can be sealed in, but the laser must sit somewhere it can be replaced. That is the ELS (External Laser Source): the laser becomes a separate module plugged into the front panel, and fiber carries its light into the optical engine inside the package.
4.2 Two examples: three Broadcom generations, and 18 light sources in one NVIDIA switch
Broadcom's three generations of CPO switches trace exactly how laser replacement evolved:
Humboldt: the lasers were already remote modules, but if a laser or the optics failed, the whole switch had to be replaced.
Bailly: the lasers became detachable and could potentially be replaced in the field.
Davisson: the laser modules are field-replaceable from the front panel.
Meta ran Bailly for 1 million device hours (at 400G-equivalent ports) without a single link flap (a link dropping and recovering); the only port issue turned out to be a faulty fiber cable.
This figure shows the first 1 million device hours of Meta's Bailly CPO test: on the left, the conclusion that no link flaps occurred; on the right, FEC statistics at 346K, 680K and 1,049K cumulative device hours, with error-correction demand not worsening over time. It is the data the CPO camp cites most often against "sealed means unreliable," but note it comes from lab stress testing.

▲ FEC statistics and link-flap record for Bailly CPO's first 1M device hours (Image source: Meta/Broadcom, via The Next Platform, 2025-10-17)
NVIDIA takes the same approach, with fewer lasers too: according to NVIDIA's figure, a pluggable uses 8 lasers per 1.6T, while CPO uses just 2 continuous-wave lasers per 1.6T, and laser power falls from about 10 W to about 2 W. Back in March 2025 NVIDIA explained that the lasers sit in front-panel pluggable ELS OSFP modules for quick diagnosis and replacement. The switch in Lambda's deployment spells it out: 144 ports of 800G, liquid cooling and 18 removable external light sources, so each light source serves 8 ports on average (STT calculation).
This figure shows the same 800G link built two ways. Top, the pluggable: laser, DSP and optics all live in one module; if anything fails, you pull the module and 1 port is affected. Bottom, CPO: the optical engines are sealed next to the chip and the lasers move to an ELS on the front panel; a laser failure means swapping only the ELS, but an optical-engine failure affects a whole group of ports.

▲ Two ways to handle a failure on the same 800G link: pluggable vs CPO + ELS (Image source: Simple Tech Trend original; data from Lambda, NVIDIA, The Register)
This figure shows what CPO actually looks like: the Quantum-X Photonics package on the left and Spectrum-X Photonics on the right, with the switch chip in the middle and a ring of co-packaged silicon-photonics optical engines around it. Compare it with the previous figure and you can see why an optical engine cannot be removed on its own, and why the lasers have to move outside.

▲ NVIDIA Quantum-X and Spectrum-X Photonics switch packages (Image source: NVIDIA Technical Blog, 2025-08-18)
4.3 Where the industry stands: how reliability is "counted"
NVIDIA says CPO is 15x more reliable, and Lambda offers a physical reason: in its measurements the median CPO optics temperature was 36°C, versus 51°C for pluggables. Lasers and optics age faster when hot, so liquid cooling plus moving the lasers to the front panel lets the components themselves live longer.
But one key term needs to be kept separate: blast radius. High reliability means "how often it fails"; blast radius means "how much a single failure affects." CPO improves the first and enlarges the second. The Register notes that blast radius was one of the biggest barriers to CPO adoption and that early testing suggests the worry may be overblown; yet Meta's MTBF comparison uses lab stress data for CPO and real data-center data for pluggables, so the two are not yet on the same basis.
Remember this: ELS solves "can the part that fails most often be replaced," not "what happens when an optical engine fails"; the latter has to be proven with field data.
5. One table to break down the two things
Item | How far the signal travels (thing one) | What happens when the laser fails (thing two) |
Question it answers | How far electricity travels before becoming light | Where the most failure-prone part sits |
Pluggable approach | 35–40 cm trace + DSP to repair the signal | Laser inside the module; pull and swap the module |
CPO approach | Under 0.5 inch, no DSP | Laser moved to a front-panel ELS; optical engine sealed |
Key numbers | Loss 22 dB → ~4 dB | 100 FIT per laser; 1,024 lasers ≈ one failure every 13 months |
What it decides | Power per port (800G from ~16 W to 3.5 W) | Maintenance model and blast radius |
Cost of improving it | Optical engine goes into the package and can't be removed | Extra fiber and connectors add loss and cost |
Who is pushing it | NVIDIA, Broadcom, TSMC COUPE, NTT | ELS module makers; early deployers such as Meta and Lambda |
How it is measured | pJ/bit, channel loss in dB | FIT, MTBF, link flaps, replacement unit |
Next step | 400G per lane makes long traces even harder | Moving from lab data to multi-year field data |
Remember this: thing one decides how much power CPO saves; thing two decides how fast CPO gets adopted at scale.
6. Back to CPO: every option is doing the same thing
Treat the two things as two axes and the options on the market line up in one table. They are all looking for the same balance: an electrical path short enough, and parts that can still be swapped.
Option | How far the signal travels | DSP? | What you replace when optics fail | Representative companies |
Pluggable (DSP) | To the front panel, 35–40 cm | Yes | Whole module | Innolight, Eoptolink, Coherent |
LPO/LRO | To the front panel | Removed or halved | Whole module | Arista, Meta (test comparison) |
USFP (400G per lane) | To the front panel | Yes | Whole module | NVIDIA, Cisco |
NPO | A few cm from the chip | Usually no | Pull the optical engine module | Alibaba, Innolight, Eoptolink |
CPO + ELS | Millimeters inside the package | No | Laser: swap the ELS; optical engine: a bigger unit | NVIDIA, Broadcom, NTT |
This figure places the five options: the horizontal axis is energy per bit (further left saves more power) and the vertical axis is how big a piece you replace when optics fail (higher is easier to fix). The top-left corner is where everyone wants to be: low power and easy to fix. No option is there yet; each can only get close to one side.

▲ Positioning map: energy per bit vs what you replace on failure; LPO and USFP positions are STT estimates (Image source: Simple Tech Trend original; data from Broadcom, Meta, NVIDIA/Cisco)
6.1 Pluggables: trading power for serviceability
Pluggables have a mature supply chain and are easy to swap. The cost is about 14 to 18 W per 800G port. LPO drops the DSP and cuts power noticeably, but the signal still has to reach the front panel, and longer channels get harder; Meta's data shows CPO still uses 35% less power per lane than LPO.
6.2 USFP: the pluggable camp's answer
USFP (Ultra-dense Small Form-factor Pluggable), announced by NVIDIA and Cisco in October, is the pluggable path to the next generation: 400G per lane, 16 lanes in the first modules and 32 or more later for 12.8T in total. Compared with 200G-per-lane pluggables it offers 4x bandwidth density and about 1.3x power efficiency, and supports up to 100 W without a dedicated cooling circuit. Both companies say plainly that the design is meant to keep the serviceability and deployment flexibility of pluggables.
This figure shows how Cisco positioned USFP in its pre-OCP briefing: 200G and 400G per lane, 6.4T over 16 lanes and 12.8T over 32 lanes, 4x bandwidth density, 1.3x power efficiency, with Amphenol and TE as ecosystem partners. It is the option that gives no ground on thing two (easy to fix) and only tries to catch up on thing one (power).

▲ Cisco and NVIDIA announce USFP, the first pluggable form factor designed for 400G SerDes lanes (Image source: Cisco OCP 2026 briefing, via ServeTheHome, 2026-10-13)
1.3x efficiency versus CPO's 3.5x to 5x is a big gap. USFP exists to prove that some customers will pay a higher power bill to keep "just pull it out."
6.3 NPO: pull the optical engine closer, but keep the socket
NPO (near-packaged optics) turns the optical engine into a separate module pressed into a socket next to the switch chip. Samtec's numbers show host-side channel loss falling from about 32 dB to about 15 dB, and 3.2T NPO spec cards on show floors list power under 23 W. We broke down its structure in our NPO primer: the laser can sit outside on the front panel or inside the module, and a failed optical engine can be removed on its own.
6.4 CPO + ELS: maximum power savings, only the laser stays swappable
CPO sits at the low-power end. NVIDIA's Quantum-X Photonics is deployed at scale at Lambda, and Kress said on the earnings call that scale-out CPO is in volume production; Broadcom's Davisson draws about 3.5 W per 800G port; and NTT's PEC-2-based 102.4T optical switch is slated for commercial launch by the end of fiscal 2026, with a Broadcom switch chip and an Accton chassis.
This figure shows where NVIDIA's 3.5x power saving comes from: per 1.6T, a pluggable draws about 30 W (DSP 20 W, laser 10 W), while CPO draws about 9 W (optical engine 7 W, laser source 2 W). That works out to about 18.8 pJ/bit versus 5.6 pJ/bit (STT calculation). Note that NVIDIA said 3.5x in 2025 and 5x on the November call; the baselines may differ.

▲ Power breakdown per 1.6T: pluggable 30 W vs NVIDIA co-packaged silicon photonics 9 W (Image source: NVIDIA Technical Blog, 2025-08-18)
7. The real bottleneck: not whether it can be built, but whether there is enough proof
Thing one is largely solved: three Broadcom generations and two NVIDIA product lines have shown that a millimeter-scale electrical path works, with power falling each generation. Today's real bottleneck is proof on thing two: once the optical engine is sealed in, there is not yet enough multi-year field reliability data.
The evidence today falls into three groups: Meta's 1 million device hours (lab stress testing), Lambda's 10,000-plus GPU deployment (just switched on) and NVIDIA's "15x higher" (a vendor claim). Testing is still early too: on its November call Keysight said CPO/NPO becomes meaningful in 2027 with a bigger inflection in FY28, and MPI's (6223.TW) CPO test system Insertion 2 is expected to get its first customer qualification result only in December.
This figure shows how CPO's bottleneck shifts: today the question is "is it reliable enough," with lab data and the first deployments as evidence; in 2027–2028 it becomes "can it be built at scale": 15x optics capacity, the number of ELS lasers, and optical-engine testing and yield.

▲ CPO's bottleneck shifts from "reliable enough?" today to "can it be built at scale?" in 2027–2028 (Image source: Simple Tech Trend original; data from Meta, Lambda, NVIDIA, Keysight, MPI, APC)
What would flip the picture? We watch two conditions:
Multi-year field data shows that a CPO switch failure has no bigger impact than a pluggable failure. The premium for "easy to fix" would then shrink, and so would the room for USFP and LPO.
400G per lane makes long traces unworkable. Doubling the signal frequency widens the gap on thing one; USFP is the pluggable camp's answer here, and whether it can hold power down at 400G decides how long pluggables can last.
STT's view: in scale-out, CPO is additive, not an immediate replacement. By pushing CPO and USFP at the same time, NVIDIA is hedging across two supply chains; CPO shipments will grow clearly in 2027, but large-scale replacement of pluggables will have to wait until field data and test capacity are in place in 2028.
8. Next time you see a CPO headline, ask these three questions
How far does the electrical signal travel from the chip to the optics? Millimeters means CPO, centimeters means NPO, tens of centimeters means pluggable. The longer the path, the more a DSP is needed and the higher the power; when a headline says "X times less power," first check what it is compared against.
When the laser fails, what gets replaced? The whole module, the front-panel ELS, or the entire switch? This sets the maintenance model, and decides whether ELS module makers and polarization-maintaining fiber makers have a market.
How many ports does one failure affect, and is the data from the lab or the field? Reliability has two parts: "how often it fails" and "how much one failure affects." Lab stress tests and multi-year data-center data carry very different weight.
Summary
On the surface, CPO volume production is "light replacing copper," but underneath are two things. Thing one is how far the electrical signal travels: CPO shrinks a 35–40 cm trace to under 0.5 inch, cuts loss from 22 dB to about 4 dB, removes the DSP, and takes an 800G port from well over 10 W to 3.5 W.
Thing two is what happens when the laser fails: the optical engine is sealed next to the chip and cannot be replaced on its own. The industry's answer is to move the most failure-prone part, the laser, to a front-panel ELS, as Broadcom's three generations and NVIDIA's 18 light sources per switch show. What remains is the optical engine itself, which has to be proven with field data.
The signal most worth tracking: whether early deployers such as Lambda and Meta publish field failure rates and replacement records for CPO switches over the next year. Once that data is out, we will know how much of the pluggable market CPO can take in 2028.
This article is for technology and industry trend analysis only and does not constitute investment advice.
References
"Colette Kress keeps Nvidia rolling in the deep networking waters without Jensen," SDxCentral, 2026-11-17, https://www.sdxcentral.com/news/colette-kress-keeps-nvidia-rolling-in-the-deep-networking-waters-without-jensen/
"Lambda announces the world's first large-scale CPO deployment of NVIDIA Photonics switches," Lambda, 2026-11-16, https://lambda.com/blog/worlds-first-large-scale-deployment-of-nvidia-photonics-switches-with-cpo
"Scaling AI Factories with Co-Packaged Optics for Better Power Efficiency," NVIDIA Technical Blog, 2025-08-18, https://developer.nvidia.com/blog/scaling-ai-factories-with-co-packaged-optics-for-better-power-efficiency/
"A New Era in Data Center Networking with NVIDIA Silicon Photonics-based Network Switching," NVIDIA Technical Blog, 2025-03-27, https://developer.nvidia.com/blog/a-new-era-in-data-center-networking-with-nvidia-silicon-photonics-based-network-switching/
"The Third Time Will Be The Charm For Broadcom Switch Co-Packaged Optics," The Next Platform, 2025-10-17, https://www.nextplatform.com/connect/2025/10/17/the-third-time-will-be-the-charm-for-broadcom-switch-co-packaged-optics/1635588
"Broadcom intros 'Bailly,' a co-packaged optics networking switch," Laser Focus World, 2023-03-01, https://www.laserfocusworld.com/optics/article/14290374/broadcom-intros-bailly-a-copackaged-optics-networking-switch
"Copackaged optics have officially found their killer app," The Register, 2025-11-22, https://www.theregister.com/2025/11/22/cpo_ai_nvidia_broadcom/
"NVIDIA and Cisco Introduce New Pluggable Optics Form Factor to Scale AI Factories," NVIDIA Newsroom, 2026-10-12, https://nvidianews.nvidia.com/news/nvidia-and-cisco-introduce-new-pluggable-optics-form-factor-to-scale-ai-factories
"Cisco OCP AI networking announcements with NVIDIA," ServeTheHome, 2026-10-13, https://www.servethehome.com/cisco-ocp-ai-networking-announcements-nvidia/
"NTT R&D Forum: IOWN photonics-electronics convergence devices" (in Japanese), EE Times Japan, 2026-11-18, https://eetimes.itmedia.co.jp/ee/articles/2611/18/news059.html
STT Industry Weekly 2026-W47 (Keysight and MPI earnings calls), 2026-11-23
Related reading
"To understand NPO, first understand two things: external or internal laser, integrated or discrete PD": the full NPO breakdown behind section 6.3. https://www.simpletechtrend.com/en/post/npo-key-components-laser-pd-primer-en
"To understand slow-and-wide optical interconnects, first understand two things: SerDes and die-to-die": the other side of "how far the signal travels," and why SerDes gets more expensive. https://www.simpletechtrend.com/en/post/slow-and-wide-serdes-die-to-die-primer-en
"NPO is not an appetizer for CPO": why China treats serviceability and yield as architecture choices. https://www.simpletechtrend.com/en/post/npo-is-not-a-stepping-stone-cioe-ecoc-2026-en
"OCP Global Summit 4/6: the optical bar shifts from pJ/bit to recovery time": why cloud operators now judge optical links by recovery time. https://www.simpletechtrend.com/en/post/ocp-global-summit-2026-optical-link-reliability-flap-recovery-en